  1.                          SECTION 09831
  2.  
  3.                  FIRE-RATED ACOUSTICAL BARRIERS
  4. NOTE ** This section is based on the products of the
  5.         Homasote Company, which is located at:
  6. NOTE **    P.O. Box 7240
  7. NOTE **    West Trenton, NJ  08628-0240
  8. NOTE **    Tel:  (609) 883-3300
  9. NOTE **    Fax:  (609) 530-1584
  10. NOTE **    Internet address:  http://www.homasote.com
  11. NOTE **    For local rep contact:  Sweet's Buyline 1-800-
  12.         892-1165 (#0878)
  13. NOTE ** The Homasote Company manufactures various products
  14.         for the building industry.  This section covers
  15.         only a part of their product line:  "N.C.F.R.(R)
  16.         Homasote" and "N.C.F.R.(R) Wall Shield" are Class A
  17.         fire-rated panels used for sound-deadening and
  18.         tackable applications where fire ratings are
  19.         important.  These products are made from 100
  20.         percent recycled, all wood fiber material
  21.         completely impregnated with fire retardant chemical
  22.         ingredients, treated to resist moisture, termites,
  23.         and fungi, and compressed into high density,
  24.         structural exterior building board.  The resulting
  25.         product contain no asbestos or urea formaldehyde
  26.         additives and offer constant insulation against
  27.         air, moisture, and noise penetration.
  28. NOTE **
  29. NOTE ** See The Homasote Company's other sections for non-
  30.         rated acoustical barriers, wood roof decking,
  31.         fiberboard underlayment, and acoustical wall
  32.         panels.
  33. NOTE **
  34. NOTE ** SECTION 09831 - FIRE-RATED ACOUSTICAL BARRIERS,
  35.         Copyright 1998, The Architect's Catalog, Inc.
  36.  
  37. PART 1  GENERAL
  38.  
  39. 1.1 SECTION INCLUDES
  40. NOTE ** Select paragraphs below applicable to project.
  41.  
  42.     A.  Tackable wall panels.
  43.  
  44.     B.  Ceiling paneling.
  45.  
  46.     C.  Display wall.
  47.  
  48.     D.  Tack board.
  49.  
  50.     E.  Tackable substrate for fire-rated wall covering.
  51.  
  52.     F.  Wall sheathing.
  53.  
  54.     G.  Noise-deadening resilient carpet underlayment.
  55.  
  56.     H.  Soffits.
  57.  
  58.     I.  Fire-rated garage interiors.
  59.  
  60.     J.  Interior siding.
  61.  
  62.     K.  Exterior siding.
  63.  
  64.     L.  _________________________________.
  65.  
  66. 1.2 RELATED SECTIONS
  67. NOTE ** Delete sections below not relevant to this project;
  68.         add others as required.
  69.  
  70.     A.  Section 06100 - Rough Carpentry.
  71.  
  72.     B.  Section 07260 - Vapor Retarders.
  73.  
  74.     C.  Section 07460 - Siding.
  75.  
  76.     D.  Section 09110 - Non-Load-Bearing Wall Framing.
  77.  
  78.     E.  Section 09250 - Gypsum Board.
  79.  
  80.     F.  Section 09680 - Carpet.
  81.  
  82.     G.  Section 09900 - Painting.
  83.  
  84.     H.  Section 10300 - Fireplaces and Stoves.
  85.  
  86.     I.  Section _____ - _________________________.
  87.  
  88. 1.3 REFERENCES
  89. NOTE ** Delete references from the list below that are not
  90.         actually required by the text of the edited
  91.         section; add others as required.
  92.  
  93.     A.  ASTM E 84 - Test Method for Surface Burning
  94.         Characteristics of Building Materials.
  95.  
  96.     B.  ASTM D 1037 - Test Methods of Evaluating Properties of
  97.         Wood-Base Fiber and Particle Panel Materials.
  98.  
  99.     C.  UL - Report No. R-5268.
  100.  
  101.     D.  UL Canada - File No. CR909.
  102.  
  103.     E.  ____________________________________.
  104.  
  105. 1.4 SUBMITTALS
  106.  
  107.     A.  Submit under provisions of Section 01300.
  108.  
  109.     B.  Product Data:  Manufacturer's catalog data, detail
  110.         sheets, and specifications.
  111.  
  112.     C.  Quality Assurance/Control Submittals:
  113.         1.  Manufacturer's installation instructions.
  114.  
  115. 1.5 QUALITY ASSURANCE
  116.  
  117.     A.  Manufacturer's Qualifications:
  118.         1.  Minimum 10 years experience in producing fire-rated
  119.             panels of the type specified herein.
  120.  
  121. 1.6 DELIVERY, STORAGE, AND HANDLING
  122.  
  123.     A.  Deliver materials in manufacturer's original packages.
  124.  
  125.     B.  Inspect the materials upon delivery to assure that
  126.         specified products have been received.
  127.  
  128.     C.  Report damaged material immediately to the delivering
  129.         carrier and note such damage on the carrier's freight
  130.         bill of lading.
  131.  
  132.     D.  Store materials in a dry place, indoors, or on raised
  133.         platform protected from weather damage.
  134.  
  135.  
  136. PART 2  PRODUCTS
  137.  
  138. 2.1 MANUFACTURERS
  139.  
  140.     A.  Acceptable Manufacturer:  Homasote Company, P.O. Box
  141.         7240, West Trenton, NJ 08628-0240; ASD. Tel: (609) 883-
  142.         3300, Fax: (609) 530-1584, Internet address:
  143.         http://www.homasote.com; For local rep contact:  Sweet's
  144.         Buyline 1-800-892-1165 (#0878).
  145.  
  146.     B.  Requests for substitutions will be considered in
  147.         accordance with provisions of Section 01600.
  148. NOTE ** Delete paragraph above or below; coordinate with
  149.         Division 1 requirements.
  150.  
  151.     C.  Substitutions:   Not permitted.
  152.  
  153.     D.  Provide all fire-rated panels from a single manufacturer.
  154.  
  155. 2.2 MATERIALS
  156. NOTE ** Select type of fire-rated panel from the two types
  157.         below; delete type not required for the project.
  158. NOTE **
  159. NOTE ** Nominal sizes of N.C.F.R.(R) Homasote panels are 4
  160.         by 4 feet (1.219 by 1.219 m), 4 by 8 feet (1.219 by
  161.         2.438 m), 4 by 10 feet (1.219 by 3.048 m), 4 by 12
  162.         feet (1.219 by 3.658 m), and 8 by 12 feet (2.438 by
  163.         3.658 m).  Other sizes are available on request.
  164.  
  165.     A.  N.C.F.R.(R) Homasote:  Class A fire rated, physical
  166.         properties as follows:
  167.         1.  Thickness:  1/2 inch (13 mm).
  168.         2.  Density:  34-40 pcf (544-640 kg/cubic m).
  169.         3.  Tensile Strength parallel to surface:  400-700 psi
  170.             (2,755-4,830 kPa) minimum.
  171.         4.  Transverse M.O.R.:  600-950 psi (4,140-6,555 kPa)
  172.             minimum.
  173.         5.  Hardness (Janka Ball):  275 lbs. (124 kg) minimum.
  174.         6.  Water Absorption by Volume; ASTM D 1037:
  175.             a.  2 hour immersion:  5 percent maximum.
  176.             b.  24 hour immersion):  14 percent maximum.
  177.         7.  Expansion, 50 to 90 percent relative humidity:  0.30
  178.             percent.
  179.         8.  R-value:  0.85 (0.015).
  180.         9.  Noise Reduction Coefficient:  0.20.
  181.         10. Finish:  Natural.
  182.         11. Fire Hazard Classification:  Flame Spread 25, Fuel
  183.             Contributed 0, Smoke Developed 20, per UL Building
  184.             Materials Index.
  185. NOTE ** Nominal sizes of N.C.F.R.(R) Wall Shield panels are
  186.         4 by 4 feet (1.219 by 1.219 m), 4 by 8 feet (1.219
  187.         by 2.438 m), 4 by 10 feet (1.219 by 3.048 m), and 4
  188.         by 12 feet (1.219 by 3.658 m).
  189.  
  190.     B.  N.C.F.R.(R) Wall Shield: Class A fire rated, physical
  191.         properties as follows:
  192.         1.  Thickness:  1/2 inch (13 mm).
  193.         2.  Density:  34-40 pcf (544-640 kg/cubic m).
  194.         3.  Tensile Strength parallel to surface:  400-700 psi
  195.             (2,755-4,830 kPa) minimum.
  196.         4.  Transverse M.O.R.:  600-950 psi (4,140-6,555 kPa)
  197.             minimum.
  198.         5.  Hardness (Janka Ball):  275 lbs. (124 kg) minimum.
  199.         6.  Water Absorption by Volume; ASTM D 1037:
  200.             a.  2 hour immersion:  5 percent maximum.
  201.             b.  24 hour immersion):  14 percent maximum.
  202.         7.  Expansion, 50 to 90 percent relative humidity:  0.30
  203.             percent.
  204.         8.  R-value:  0.85 (0.015).
  205.         9.  Noise Reduction Coefficient:  0.20.
  206.         10. Finish:  Natural.
  207.  
  208. 2.3 ACCESSORIES
  209. NOTE ** Installation accessories are dependent on
  210.         substrates and installation methods as recommended
  211.         by the manufacturer; select from the following
  212.         paragraphs accordingly.
  213.  
  214.     A.  Metal Frame Clips:  Manufacturer's standard clip for
  215.         securing panels to framing.
  216.  
  217.     B.  Adhesive:  APA approved panel adhesive.
  218.  
  219.     C.  Nails:  Length as required to penetrate wood framing 3/4
  220.         inch (19 mm) minimum.
  221.  
  222.     D.  Nails:  Finishing nails, length as required to penetrate
  223.         wood framing 3/4 inch (19 mm) minimum.
  224.  
  225.     E.  Screws:
  226.         1.  Wood Framing:  Coarse thread drywall type wood screw,
  227.             length as required to penetrate framing 3/4 inch (19
  228.             mm) minimum.
  229.         2.  Metal Framing:  22-25 gage, drywall type steel screw.
  230.         3.  Metal Framing:  20 gage or heavier, self-tapping
  231.             drywall type steel screw.
  232.  
  233.  
  234. PART 3  EXECUTION
  235.  
  236. 3.1 EXAMINATION
  237.  
  238.     A.  Examine substrates upon which work will be installed.
  239. NOTE ** Delete the following paragraph if panels are
  240.         applied only as carpet underlayment.
  241. NOTE **
  242. NOTE ** To prevent condensation damage within walls, it is
  243.         good building practice to install a vapor retarder
  244.         in buildings where the January temperature falls
  245.         below 40 degrees F (4.5 degrees C).
  246.  
  247.     B.  Verify framing member spacing complies with
  248.         manufacturer's requirements depending on substrates and
  249.         installation methods.
  250.  
  251.     C.  Verify environmental conditions are, and will continue to
  252.         be, maintained in accordance with manufacturer's
  253.         recommendations.
  254.  
  255.     D.  Coordinate with responsible entity to perform corrective
  256.         work on unsatisfactory substrates or conditions.
  257.  
  258.     E.  Starting work by installer is acceptance of substrate and
  259.         environmental conditions.
  260.  
  261. 3.2 PREPARATION
  262.  
  263.     A.  Follow manufacturer's instructions by separating and
  264.         allowing panels to be exposed to environmental
  265.         temperature and humidity conditions for not less than 24
  266.         hours before start of installation.
  267.  
  268.     B.  Precondition panels larger than 4 by 8 feet (1.219 by
  269.         2.438 m) panels by sprinkling with water and stacking wet
  270.         side up overnight.
  271.  
  272. 3.3 INSTALLATION
  273.  
  274. NOTE ** Homasote requires wall framing at 16 inches (400
  275.         mm) o.c. for 1/2 inch (13 mm) boards.  Edges and
  276.         ends are required to align with framing members or
  277.         be blocked for all methods.  Verify that
  278.         appropriate framing section or drawing notes
  279.         comply.
  280.  
  281.     A.  Follow manufacturer's instructions for cutting and
  282.         installation of fire rated panels.
  283.  
  284.     B.  Install panels in dry condition only.
  285. NOTE ** Select applications from paragraphs below.
  286. NOTE **
  287. NOTE ** Any wood or hardboard finish paneling, or metal or
  288.         vinyl siding applied over N.C.F.R.(R) Homasote must
  289.         be installed with nails of sufficient length to
  290.         penetrate Homasote and anchor into framing 1 inch
  291.         (25 mm) minimum.
  292. NOTE **
  293. NOTE ** Any component added to or structurally combined
  294.         with N.C.F.R.(R) Homasote when used as siding,
  295.         paneling, or underlayment, must be Fire Hazard
  296.         Classification to maintain continuity.
  297.  
  298.     C.  N.C.F.R.(R) Homasote Exterior Applications:
  299.         1.  Apply panels over wood sheathing or direct to framing
  300.             by glue-nailing or with nails only.
  301.         2.  Allow 3/16 inch (4.7 mm) gap at exposed joints, seal
  302.             with calking, and cover with battens.
  303.  
  304.     D.  N.C.F.R.(R) Homasote Interior Applications:
  305.         1.  Apply panels direct to framing or solid furring by
  306.             glue-nailing or with nails only.
  307.         2.  Apply panels to old masonry walls by glue-nailing,
  308.             provided walls are flat and solid.
  309.         3.  Allow 3/16 inch (4.7 mm) gap at butt joints, 3/8 inch
  310.             (9.5 mm) gap at floor, ceiling, and abutting framing.
  311.  
  312.     E.  N.C.F.R.(R) Homasote Underlayment Applications on Wood
  313.         Sub-Flooring:
  314.  
  315. NOTE ** Where used as underlayment, fire rating can be
  316.         maintained only when fire rated carpet and pad are
  317.         used.
  318. NOTE **
  319. NOTE ** Sub-floor must be flat (not cupped), dry, level,
  320.         and securely fastened to joists.
  321.         1.  Shim or sand sub-floor as necessary to provide a flat
  322.             surface continuity for panels.
  323.         2.  Apply underlayment panels with APA approved decking
  324.             adhesive and nails, or with nails only.
  325.         3.  Allow 3/16 inch (4.7 mm) gap at abutting edges; 3/8
  326.             inch (9.5 mm) space at walls and partitions.
  327. NOTE ** N.C.F.R.(R) Wall Shield is for use with UL listed
  328.         solid-fuel type room heaters and listed fireplace
  329.         stoves in residential type structures.  It is
  330.         approved for use with vertical flue installations
  331.         only, not for use where flue passes through panels.
  332.  
  333.     F.  N.C.F.R.(R) Wall Shield Applications:
  334. NOTE ** Locations and attachment of non-combustible spacers
  335.         and method of application of panels depends on type
  336.         of finish to be used on panel face.  Consult
  337.         manufacturer's recommendations.
  338.         1.  Space panels 1 inch (25 mm) from wall with non-
  339.             combustible spacers attached to wall and spaced as
  340.             recommended by panel manufacturer.
  341.         2.  Space panels 1 inch (25 mm) minimum and 3 inches (75
  342.             mm) maximum above floor and below ceiling.
  343.         3.  Extend panels 8 inches (203 mm) minimum each side of
  344.             projected area of back of stove or flue.
  345.  
  346. 3.4 ADJUSTING AND CLEANING
  347.  
  348.     A.  Follow manufacturer's instructions for repairing damaged
  349.         panels.
  350.  
  351.     B.  Replace panels that cannot be repaired to "as new"
  352.         condition.
  353.  
  354.  
  355.                          END OF SECTION
  356.